DT Hydrogen 0.2%/a (10)
Details
Details
Standard Measuring Range: 0.2 to 2.0 vol.% %
Number of Strokes n: 1
Time for Measurement: Approx. 1 min
Standard Deviation: ± 15 to 20 %
Color Change: Green Yellow → Turquoise Blue
Ambient Operating Conditions:
Temperature: 20 to 40 °C
Absolute Humidity: max. 50 mg H2O / L
Reaction Principle:
a) H2 + 1/2 O2 → H20
b) H2O + indicator → turquoise blue reaction product
Cross Sensitivity:
No interference by:
0.1 vol. % acetylene
6 vol. % alcohol
6 vol. % ammonia
0.5 vol. % carbon monoxide
Additional Information:
The indicating layer is heated by hydrogen concentrations of more than 10 vol.%.
The air sample must not contain additional flammable substances whose ignition temperature is below 250 °C (482 °F), as this poses an explosion risk.